DRX-TC
THERMOCOUPLE SIGNAL CONDITIONER/TRANSMITTER

Made in the USA
INFINITY
Electromagentic Compatibility
Year 2000 Compliant
What You need:
ò Your choice of the signal conditioner
ò IBM PC or compatible
ò Windows 3.1 or higher, or Windows 95
ò RJ12 connector with telephone cable
ò Adapter (DB9/25 to RJ12)
SETTING UP YOUR SYSTEM
DRN Computer Connection
INPUT TYPE
Type J, K, T, E, R, S, B, N, J DIN
Input
Range ░F
Range ░C
Input
Range ░F
Range ░C
J
-346 to 1400░F
-210 to 760 ░C
RS
-58 to 3214 ░F
-50 to 1768 ░C
K
-454 to 2500░F
-270 to 1372 ░C
B
+212 to 3300 ░F
+100 to 1820 ░C
T
-454 to 752 ░F
-270 to 400 ░C
N
-454 to 2372░F
-270 to 1300 ░C
E
-454 to 1832 ░F
-270 to 1000 ░C
JDIN
-328 to 1652 ░F
-200 to 900 ░C

DRX-TCISOLATION
Three way isolation up to 1800 V Peak for 1 minute, 345 V Peak continuous per IEC spacing. Common mode rejection 100 dB

INPUT OVER-VOLTAGE PROTECTION
250 V AC for 1 Minute

ANALOG TO DIGITAL TECHNIQUE
Dual slope

READ RATE
3 readings/second, automatic polarity

ACCURACY AT 25 ░C

  • ▒1░C for temperature above -150 ░C
  • ▒2░C for temperature below -150 ░C


  • TEMPERATURE STABILITY
    0.05 ░C/░C

    STEP RESPONSE FOR RS485 OUTPUT

    2 seconds to 99% of the final value (Filter time constant = 64)

    RESPONSE TIME

    To verify the response time, check the carriage return <CR>, it will be sent at the end of the response. You can send another command after you receive the <CR>.
    i.e. send: *01X01 / response: 01X01<DATA><CR>
    Note: 01 is address.

    Signal Conditioner
    WARM UP TO RATED ACCURACY
    30 minutes

    INPUT POWER

    10 to 32 Volt

    DC POWER CONSUMPTION

    2.4 Watts (100 mA at 24 V DC)

    OPERATING AMBIENT

    -5 to +55 ░C

    STORAGE TEMPERATURE

    -40 to +85 ░C

    RELATIVE HUMIDITY

    90% at 40 ░C non-condensing

    Help Price List Specifications Print Manual Manuals Home